Detects smoke by the size of particles in the air.
Protection from false alarms
Does not react to water vapor.
Patented smoke chamber
Protects the smoke sensor from dust, dirt, and insects.
Dangerous temperature detection
Sensitive element
according to the requirements for Class A1R heat detectors
Requirements of EN 54-5 and BS 5446-2 standards.
High temperature alarm
at temperatures above 147°F
Temperature spike alarm
when the temperature rises by more than 50°F in 1 minute or less
Carbon monoxide (CO) detection
Sensitive element
chemical CO sensor
Alarm if accumulated dose of CO is exceeded
over 50 ppm (0.005%) — in 90 minutes or less over 100 ppm (0.01%) — in 40 minutes or less over 300 ppm (0.03%) — in 3 minutes
CO concentration exceeding 400 ppm (0.04%) within a span of 3 hours poses a life-threatening risk. The detector will cease notifications regarding hazardous carbon monoxide levels once the concentration decreases to 50 ppm (0.005%) within a 1-minute duration.
Sensor service life
10 years
After 10 years of operation, the detector must be replaced with a new one.
Additional features
Built-in siren
volume 85 dB at a distance of 9 ft
Sound notification of alarms. Remains active until the reason for triggering is eliminated or until the user manually disables the notification.
Interconnected fire detectors alarms
via primary interconnection
If one of the fire detectors in the system detects a threat, it sends an alarm to the hub. Within 20 seconds, the hub initiates an interconnected alarm and sends data to Ajax apps.
via fallback interconnection
At the same time with notifying the hub, the initiating detector sends an alarm directly to other detectors. All connected detectors activate the buzzer within a minute. It will work even in the worst-case scenario of losing connection with the hub.
An LED indicator on the device enclosure lights continuously when powered by an external power source. If the device draws power from the backup battery, the LED indicator lights up once every 56 seconds. This indication complies with the requirements stipulated in EN 14604 and EN 50291 standards.
yellow is a malfunction indication
An LED indicator on the device enclosure lights up to signal detected malfunctions. This can occur in instances such as battery depletion, smoke chamber contamination, or reaching the end of the service life.
red is a fire alarm indication
An LED indicator on the device enclosure lights up when the detector registers a fire alarm.
Button on the front panel of the detector
In normal mode, when pressed, it starts the smoke chamber test. In the event of an alarm or malfunction, the pressing turns off the detector sound notification.
External power supply
110–240 V~, 50/60 Hz
The phase and neutral cables from the external power supply should be connected to the WAGO terminals on SmartBracket mounting panel. To remove the detector from SmartBracket, there is no need to disconnect the power cables.
Recommendations
The device is designed for indoor installation only. SmartBracket mounting panel allows adjusting the position of the detector even after installation.
Sabotage protection
Tamper alarm
Notifications on attempts to detach the detector from the surface or remove it from the mounting panel.
The time required to detect a communication loss depends on the settings for the number of undelivered data packages (specified in the Jeweller or Jeweller/Fibra settings).