OBUbeD
FireProtect 2 SB (Heat/CO) Jeweller
Wireless combined heat and CO detector with sealed batteries
yA5lgs
9td1WlCommunication
Jeweller communication technology
Proprietary wireless technology for transmission of alarms and events.
Features:
- Two-way communication.
- Protection against device spoofing.
- Block encryption featuring a floating key.
- Instant notifications.
- Remote configuration via the Ajax apps.
Radio frequency bands
866.0 – 866.5 MHz
868.0 – 868.6 MHz
868.7 – 869.2 MHz
905.0 – 926.5 MHz
915.85 – 926.5 MHz
921.0 – 922.0 MHz
Depends on the region of sale.
Maximum effective radiated power (ERP)
up to 20 mW
Automatic power control to reduce power consumption and radio interference.
Radio signal modulation
GFSK
Radio communication range
up to 5,500 ft
Between the detector and a hub (or radio signal range extender) in an open space.
Encryption of radio communication
All the data stored and transmitted are protected by block encryption with a floating key.
Radio frequency hopping
To prevent radio interference and jamming.
Sensitive elements
heat sensor
CO (carbon monoxide) sensor
Dangerous temperature detection
Sensitive element
according to the requirements for Class A1R heat detectors
Requirements of EN 54-5 and BS 5446-2 standards.
High temperature alarm
at temperatures above 147°F
Temperature spike alarm
when the temperature rises more than 50°F in 1 minute or less
Carbon monoxide (CO) detection
Sensitive element
chemical CO sensor
Alarm if accumulated dose of CO is exceeded
more than 50 ppm (0.005%) — no more than in 90 minutes
more than 100 ppm (0.01%) — no more than in 40 minutes
more than 300 ppm (0.03%) — no more than in 3 minutes
CO concentration of 400 ppm (0.04%) within 3 hours can be life-threatening. The detector stops notifying about the dangerous level of carbon monoxide when the concentration drops to 50 ppm (0.005%) within one minute.
Sensor life
10 years
After 10 years of operation, the detector must be replaced with a new one.
Additional features
In-built siren
volume 85 dB at a distance of 9 ft
Sound notification of alarms. Active until the reason for triggering is eliminated or until the user disables notification.
Interconnected fire detectors alarms
via primary interconnection
If one of the fire detectors in the system detects a threat, it sends an alarm to the hub. Within 20 seconds, the hub initiates an interconnected alarm and sends data to Ajax apps.
LED indication
green is a power indication
A LED indicator on the device enclosure lights up once every 56 seconds. The indication meets the requirements of EN 50291.
yellow is an indication of malfunctions
A LED indicator on the device enclosure lights up when malfunctions are detected. For example, if the battery is low.
red is an indication of fire alarms
A LED indicator on the device enclosure lights up when the detector registers a fire alarm.
Button on the front panel of the detector
In normal mode, runs the detector test when pressed. In the event of an alarm or malfunction, the pressing turns off the detector sound notification.
Recommendations
The device is designed only for indoor installation. SmartBracket mounting panel allows adjusting the position of the detector after installation.
Anti-sabotage protection
Tampering alarm
Alerts of attempts to detach the detector from the surface or remove the mounting panel.
Protection against spoofing
device authentication
Detection of communication failure
within 15 minutes
The time to detect communication loss depends on the settings for the number of undelivered data packages (specified in the Jeweller or Jeweller/Fibra settings). The polling interval is fixed at 300 seconds.
Power supply
For FireProtect 2 SB (Heat/CO)
2 non-replaceable lithium batteries
10 years of battery life.
Enclosure
Dimensions
1.71″ × 3.39″ × 3.39″
Weight
5.11 oz
Operating temperature range
from 32°F to 122°F
Operating humidity
up to 80%
Protection class
IP20
Colours
Black
White
Complete set
FireProtect 2 SB (Heat/CO) Jeweller
SmartBracket mounting panel
Installation kit
Quick start guide
hQt5e6
FireProtect 2 SB (Heat/CO) Jeweller
FireProtect 2 SB (Heat/CO) Jeweller
Fire detection and fire alarm systems. Heat detectors/Point detectors
EN 54-5:2017+A1:2018 except cl. 4.2.2.1
Electrical apparatus for the detection of carbon monoxide in domestic premises
UkrTEST of SE “Ukrmetrteststandart”
EN 50291-1:2018
Radio Equipment Directive (RED)
Certificate issued by MiCOM Labs
EN 300 220-1 V3.1.1
EN 300 220-2 V3.2.1
Restriction of Hazardous Substances Directive (RoHS)
Shenzhen NTEK Testing Technology Co.
EN IEC 63000:2018
Electromagnetic Compatibility Directive (EMC)
Certificate issued by MiCOM Labs
EN 301 489-1 V2.2.3
EN 301 489-3 V2.1.1
Low Voltage Directive (LVD)
Certificate issued by MiCOM Labs
EN 62368-1:2014+A11:2017
EN 62479:2010
FCC ID
Certificate issued by MiCOM Labs
2AX5VFIHTCOJ1
IC ID
Certificate issued by MiCOM Labs
26860-FIHTCOJ1
PSTI UK
Schedule 1